Linear drives M1 1000 N

M1 1000N

For opening and closing windows for smoke and heat extraction and daily ventilation



features


  •  24 V DC drive for SHE- and ventilation application
  •  up to max. 1000 N pressing force
  •  motor unit in aluminium tube
  •  fast operational speeds
  •  opening time ≤ 60 sec. up to 850 mm stroke during nominal operation
  •  suitable for synchronised operation, depending on the model
  •  automatic cut-off via integrated current detection or via externalsynchronised control

different variants:


M1/300-1000N/LA/EV1/RWA (6690303),M1/500-1000N/LA/EV1/RWA (66900503), M1/750-1000N/LA/EV1/RWA (66900753), M1/1000-1000N/LA/EV1/RWA (66901003), M1/300-1000N/SG/EV1/RWA (66900309), M1/500-1000N/SG/EV1/RWA (66900509), M1/750-1000N/SG/EV1/RWA (66900759), M1/ 1000-1000N/SG/EV1/RWA (66901009)

SHE:

RWA

ventilation:

Lueftung

Go back

  • data

  • BOQ texts

  • drawing

  •        
  • accessories

  • note

  •    
  • download

             

technical voltage

24 V DC (-20 % / +25 %)

technical draw

2.5 amp

cut-off

internal (LA) or external via a synchro module (SM) depending on version

pressing force

1000 N

tractive force


nominal clamping force

2000 N

stroke width

up to 1000 mm

min. casement height at stroke length


dimensions

Ø 50 x (stroke + approx. 410 mm) (diameter x length)

speed of operation

M1/.../LA approx. 16.6 mm/sec. M1/.../SG approx. 14.6 mm/sec.

power supply cable

M1/.../LA 2 x 1.5 mm²

M1/../SG 2 x 1.5 mm² and 3 x 0.5 mm²; length at least 2 m; silicon white

start-up time

3 Min. (ED/ON), 7 Min. (AD/OFF)

service life

> 10.000 ventilation cycles at nominal load

range of temperature

-5 °C to +75 °C

IP protection class

IP 54 according to DIN EN 60 529

housing

aluminium tube

colour

EV1/silver, anodized

special colours

RAL colours on request

included in delivery


type of construction tested


acoustical measurement


dimensional drawing DXF


M1 1000N RWA D M1_1000N_RWA_D.dxf (437.5 KiB)

dimensional drawing DXF

M1 1000N RWA D M1_1000N_RWA_D.dxf (437.5 KiB)
Hinweis zum Einbau

Caution:
With the installation of two drives on one window the appropriate synchro module must be ordered. Order motor type according to application with or without signal generator (SG) or power cut-off (LA).

Note:
Please select brackets consistent with the mounting situation and order separately.

When dimensioning the power supply and the cable cross-sections for the supply
lines to the motors as a function of the control panels used, the increased
currents associated with start-up torques must be taken into account!

Go back