Linear drives M2 Tandem 500N

M2 Tandem 500N

For opening and closing casements, dome lights and skylights for smoke and heat extraction and daily ventilation



features


  •  24 V DC drive for SHE- and ventilation application
  •  compact motor unit in rectangular aluminium profile
  •  automatic switch off by current of detection
  •  tandem operation without additional external tandem control
  •  well-priced motor for stroke forces of 2 x 500 N in tandem operation
  •  tandem function with blocking protection drive

different variants:


M2/200-500N/TD/LA/EV1/RWA ( 64001290), M2/300-500N/TD/LA/EV1/RWA (64001390), M2/500-500N/TD/LA/EV1/RWA (640001590)

SHE:

RWA

ventilation:

Lueftung

Go back

  • data

  • BOQ texts

  • drawing

  •        
  • accessories

  • certificate

  • note

  •    
  • download

             

technical voltage

24 V DC (-15 % / +25 %)

technical draw

approx. 1 amp

cut-off

integrated electronic power cut-off and blockage protection cut-off for the opening procedure (deploy drive rod)

pressing force

500 N

tractive force

500 N

nominal clamping force

2000 N

stroke width

up to 500 mm

min. casement height at stroke length


dimensions

length x 60 x 41 mm, see illustration

speed of operation

approx. 8.3 mm/sec. at rating load and nominal load

power supply cable

4 x 0.5 mm²; length at least 1.50 m; silicon white

start-up time

3 min. (ED/ON), 7 min. (AD/OFF)

service life

> 10.000 ventilation cycles at nominal load

range of temperature

-5 °C to +75 °C

IP protection class

IP 54 according to DIN EN 60 529

housing

rectangular aluminium profile

colour

EV1/silver, anodized

special colours

RAL colours on request

included in delivery


type of construction tested


acoustical measurement


dimensional drawing DXF


M2 500N TD LA RWA D M2_500N_TD_LA_RWA_D.dxf (417.2 KiB)
Hinweis zum Einbau

Note:
Please select brackets consistent with the mounting situation and order separately.

Note:
For tandem operation please order two drives.

When dimensioning the power supply and the cable cross-sections for the supply lines to the motors as a function of the control panels used, the increased currents associated with start-up torques must be taken into account!

Zertifikate
CE

Go back