SHE control panel, TRZ-Plus 2A

TRZ Plus 2A
SHE control system 24 V DC for the electromotive smoke and heat extraction and for daily ventilation in staircases

features


• 2 amp current supply
• including daily ventilation function
• one SHE group (RG) and one ventilation group (LG)
• adjustable special functions
• PC Service-Port-Interface for extended configuration possibilities
• built-in maintenance timer
• integrated 230 V AC / 24 V DC power supply, emergency power
  accumulators and charging unit for 72 hours-guaranteed-function in case of
  power failure
• expandable via optional modules
• TÜV type approved
• approved according to prEN 12101-9 / EN 12101-10


different variants:

TRZ Plus 2A/Blau (62500030), TRZ Plus 2A/Gelb (62500040), TRZ Plus 2A/Grau (62500010), TRZ Plus 2A/Orange (62500050), TRZ Plus 2A/Rot (62500020)

SHE:

RWA

ventilation:

Lueftung


possible connections

  • drives 24 V DC with overall current consumptions of max. 2 amp with own power cut-off or with limit switch
  • 10 SHE manual call points RBH/3A...
  • 10 automatic detectors in 2-wire system
  • 10 external vent switches, open/stop/closed (with or without LED open)


expandable with

  • one additional module SHE manual call point TRZ/RBH-Basic for installation in the front door, please order separately
  • one additional module TRZ/WRMAS-Basic for connection of one wind-/rain detector (WRM/2 24V) or 1 rain detector (RM/2 24V), please order separately,
  • in each case one connection for potential-free report: SHE activated (NO=normally open contact) and malfunction (NC= normally closed contact); 24 V / max. 0.5 amp

Go back

  • data

  • BOQ texts

  • drawing

  •        
  • accessories

  • note

  •    
  • download

             

operating voltage

230 V AC / 50 Hz (+-10) / 24 V DC

system voltage

27 V DC (nominal) (-25 % / +10 %), smoothed
2 x 12 V / 1.2 Ah; with monitoring function for low voltage, wire breakage & fuse failure

voltage output for motor units

27 V DC (nominal) (-25 % / +10 %)

max. current supply

2 amp (nominal) 30 % ED (at 10 min.)

dimensions

220 x 146 x 83 mm

range of temperature

-5 °C to +40 °C

IP protection class

IP 30 according to DIN EN 60 529

type of construction tested

TÜV, Registration-No. 44 780 09 375661

housing

plastic (polystyrol) for surface mounting

colour

blue, yellow, grey, orange and red

dimensional drawing DXF


TRZ Plus 2A D TRZ_Plus_2A_D.dxf (847.6 KiB)

accessories

Zusatzmodul TRZ/WRMAS-Basic (61900090), Zusatzmodul RWA-Bedienstelle TRZ/RBH-Basic (61900080)), VdS zugelassene RWA-Bedienstelle RBH/3A/VdS (60000294), VdS zugelassene RWA-Bedienstelle RBH/3A/SU/VdS (60000279), RWA-Bedienstelle RBH/3A/Blau (60000298), RWA-Bedienstelle RBH/3A/Gelb (60000299), RWA-Bedienstelle RBH/3A/Grau (60000297), RWA-Bedienstelle RBH/3A/Orange (60000301), RWA-Bedienstelle RBH/3A/Rot (60000295), RWA-Bedienstelle RBH/3A/SU/Blau (60000277), RWA-Bedienstelle RBH/3A/SU/Gelb (60000278), RWA-Bedienstelle RBH/3A/SU/Grau (60000275), RWA-Bedienstelle RBH/3A/SU/Orange (60000262), RWA-Bedienstelle RBH/3A/SU/Rot (60000276), RWA-Bedienstelle RBH/3A/ALU/Blau (60001298), RWA-Bedienstelle RBH/3A/ALU/Gelb (60001299), RWA-Bedienstelle RBH/3A/ALU/Grau (60001297), RWA-Bedienstelle RBH/3A/ALU/Orange (60001300), RWA-Bedienstelle RBH/3A/ALU/Rot (60001295), RWA-Bedienstelle RBH/3A/SU/ALU/Blau (60001398), RWA-Bedienstelle RBH/3A/SU/ALU/Gelb (60001399), RWA-Bedienstelle RBH/3A/SU/ALU/Grau (60001397), RWA-Bedienstelle RBH/3A/SU/ALU/Orange (60001400), RWA-Bedienstelle RBH/3A/SU/ALU/Rot (60001395), Wetterschutzhaube WSH/Blau (95114350), Wetterschutzhaube WSH/Gelb (95114370), Wetterschutzhaube WSH/Grau (95114360), Wetterschutzhaube WSH/Orange (95114380), Wetterschutzhaube WSH/Rot (95114400), Ersatzglasscheiben EGL (95240451), Ersatzschlüssel ES-RBH/Blau (20202031), Ersatzschlüssel ES-RBH/Gelb (20202030), Ersatzschlüssel ES-RBH/Grau (20202032), Ersatzschlüssel ES-RBH/Orange (20202010), Ersatzschlüssel ES-RBH/Rot (20202029), Ersatzschlüssel ES-RBH/M (20202011), Lüftungstaster LTA 25/AP (60000461), Lüftungstaster LTA 25/UP (60000460), Lüftungstaster LTA 11/AP (60000490), Lüftungstaster LTA 11/UP (60000730), Lüftungs-Schlüsseltaster LTA 12/AP (60000481), Lüftungs-Schlüsseltaster LTA 12/UP (60000465), Lüftungs-Schlüsseltaster LTA 13(AP (95220151), Profilhalbzylinder SZ10 (94810900), Wahlschalter Hand/Automatik WHA-14/AP (60000771), Wahlschalter Hand/Automatik WHA-14/UP (60000770), Wind- und Regenmelder WRM/2 24V (13360000531), Regenmelder RM/2 24V (13360000385), Standrohr SR-400 (21100180), Temperatursensor TS-1030/AP (2500098), Temperatursensor TS-1030/UP (20402010), Elektronischer Temperatursensor TSE-53 (20402020), Feuchte-Sensor FS-3095/AP (20402017), Feuchte-Sensor FS-3095/UP (20402016), Elektronische Alarmsirene AG-026/R (Rot) (10001001), Elektronische Alarmsirene AG-026/W (weiß) (10001000), VdS zugelassener universal Wärmemelder UTD 523 Klasse A1 (20202147), VdS zugelassener universal Wärmemelder UTD 523 Klasse A1/MS (62005251), VdS zugelassener universal Wärmemelder UTD 523 Klasse A2 (20202148), VdS zugelassener universal Wärmemelder UTD 523 Klasse A2/MS (62005252), VdS zugelassener universal Wärmemelder UTD 523 Klasse B (20202149), VdS zugelassener universal Wärmemelder UTD 523 Klasse B/MS (62005253), VdS zugelassener lichtoptischer Rauchmelder MSD 523 (20202139), VdS zugelassener lichtoptischer Rauchmelder MSD 523/MS (62005300), Meldersockel USB 501-6 (20202135), Ballwurfschutz BWS-9 für automatische Melder (20202214), TRZ UP-Einbauset (13320200400), Service Port USB Konfigurationskabel inkl. Software (3000100),

dimensional drawing DXF

TRZ Plus 2A D TRZ_Plus_2A_D.dxf (847.6 KiB)

note for installation

For mounting underneath plaster a flush mounting set UPR-TRZ is required.
Please order separately.
 
 

note

The Service Port Software is required for extended configuration possibilities.
Please order separately.

Go back