Compact control panel 2A

Kompaktzentrale 2A
For smoke heat extraction and daily ventilation to control 24 V DC linear drives and chain motors

features


• SHE control panel for opening and closing of smoke vents in case of fire and ventilation
• Control of 24 V DC motors with their own load or limit with a total power consumption of max. 2A.
• function “daily ventilation”
• one SHE group and one ventilation group
• 24 V power supply, emergency power batteries and charging unit, parallel operation, 72 hours of functioning guaranteed in case of power failure
• line monitoring of alarm circuits (autom. detectors and SHE man. call points)
• line monitoring of the connected drives
• optical malfunction alarm
• separately fused power input 230 V AC / 50 Hz
• hinged door or cover, lockable
conforms to current state-of-the-art standards• processor controlled
• versatile connection facilities
• service port interface included
• TÜV type tested
• tested according to DIN EN 12101-10

item number:

13362501200

SHE:

RWA

ventilation:

Lueftung


possible connections

  • linear drives 24 V DC with integrated electronic power cut-off, tandem power cut-off, synchro module or chain motors 24 V DC with limit switches
  • overall power consumption of all motors connected max. 2 A
  • 10 automatic detectors with 2-wire-technology, optical smoke detectors and/or detectors of heat differential and/or detectors of maximum heat or monotoring resistor ex factory via the final fuse attached
  • 10 external ventilation switches “Open/Stop/Closed” (e.g. type LTA 25)
  • 24 V DC siren or flashing lights, max 100 mA
  • to connect 1 wind-/rain detector (e.g. type WRM 24V, WRM2) or 1 rain detector (e.g. RM, RM2) Only with TRZ Plus Comfort or with additional module WRMAS.
  • in each case one connection for potential-free report SHE activated (NO= normally Open contact) and malfunction (NC= normally closed contact): 24V / max. 0.5 A Only with TRZ Plus Comfort or with additional module WRMAS.

Go back

  • data

  • drawing

  •        
  • accessories

  • note

  •    
  • download

             

operating voltage

230 V AC / 50 Hz, (±10 %)

system voltage

27 V DC (nominal) (-30 % / +10 %)
2 x 12 V / 1,2 Ah

voltage output for motor units

27 V DC (nominal) (-30 % / +10 %)

max. current supply

2 amp (nominal) 30 % ED (at 10 min.)

dimensions

300 x 300 x 132mm

range of temperature

-5 °C to +40 °C

IP protection class

IP 30 according to DIN EN 60 529

type of construction tested

44 780 09 375661

housing

Tür Stahlblech, Einbaurahmen Kunststoff

colour

grey, similar to RAL 7035

dimensional drawing DXF


TRZ Plus 2A UP D TRZ_Plus_2A_UP_D.dxf (6.4 MiB)

accessories

Zusatzmodul TRZ/WRMAS-Basic (61900090), VdS zugelassene RWA-Bedienstelle RBH/3A/VdS (60000294), VdS zugelassene RWA-Bedienstelle RBH/3A/SU/VdS (60000279), RWA-Bedienstelle RBH/3A/Blau (60000298), RWA-Bedienstelle RBH/3A/Gelb (60000299), RWA-Bedienstelle RBH/3A/Grau (60000297), RWA-Bedienstelle RBH/3A/Orange (60000301), RWA-Bedienstelle RBH/3A/Rot (60000295), RWA-Bedienstelle RBH/3A/SU/Blau (60000277), RWA-Bedienstelle RBH/3A/SU/Gelb (60000278), RWA-Bedienstelle RBH/3A/SU/Grau (60000275), RWA-Bedienstelle RBH/3A/SU/Orange (60000262), RWA-Bedienstelle RBH/3A/SU/Rot (60000276), RWA-Bedienstelle RBH/3A/ALU/Blau (60001298), RWA-Bedienstelle RBH/3A/ALU/Gelb (60001299), RWA-Bedienstelle RBH/3A/ALU/Grau (60001297), RWA-Bedienstelle RBH/3A/ALU/Orange (60001300), RWA-Bedienstelle RBH/3A/ALU/Rot (60001295), RWA-Bedienstelle RBH/3A/SU/ALU/Blau (60001398), RWA-Bedienstelle RBH/3A/SU/ALU/Gelb (60001399), RWA-Bedienstelle RBH/3A/SU/ALU/Grau (60001397), RWA-Bedienstelle RBH/3A/SU/ALU/Orange (60001400), RWA-Bedienstelle RBH/3A/SU/ALU/Rot (60001395), Wetterschutzhaube WSH/Blau (95114350), Wetterschutzhaube WSH/Gelb (95114370), Wetterschutzhaube WSH/Grau (95114360), Wetterschutzhaube WSH/Orange (95114380), Wetterschutzhaube WSH/Rot (95114400), Ersatzglasscheiben EGL (95240451), Ersatzschlüssel ES-RBH/Blau (20202031), Ersatzschlüssel ES-RBH/Gelb (20202030), Ersatzschlüssel ES-RBH/Grau (20202032), Ersatzschlüssel ES-RBH/Orange (20202010), Ersatzschlüssel ES-RBH/Rot (20202029), Ersatzschlüssel ES-RBH/M (20202011), Lüftungstaster LTA 25/AP (60000461), Lüftungstaster LTA 25/UP (60000460), Lüftungstaster LTA 11/AP (60000490), Lüftungstaster LTA 11/UP (60000730), Lüftungs-Schlüsseltaster LTA 12/AP (60000481), Lüftungs-Schlüsseltaster LTA 12/UP (60000465), Lüftungs-Schlüsseltaster LTA 13(AP (95220151), Profilhalbzylinder SZ10 (94810900), Wahlschalter Hand/Automatik WHA-14/AP (60000771), Wahlschalter Hand/Automatik WHA-14/UP (60000770), Wind- und Regenmelder WRM/2 24V (13360000531), Regenmelder RM/2 24V (13360000385), Standrohr SR-400 (21100180), Temperatursensor TS-1030/AP (2500098), Temperatursensor TS-1030/UP (20402010), Elektronischer Temperatursensor TSE-53 (20402020), Feuchte-Sensor FS-3095/AP (20402017), Feuchte-Sensor FS-3095/UP (20402016), Elektronische Alarmsirene AG-026/R (Rot) (10001001), Elektronische Alarmsirene AG-026/W (weiß) (10001000), VdS zugelassener universal Wärmemelder UTD 523 Klasse A1 (20202147), VdS zugelassener universal Wärmemelder UTD 523 Klasse A1/MS (62005251), VdS zugelassener universal Wärmemelder UTD 523 Klasse A2 (20202148), VdS zugelassener universal Wärmemelder UTD 523 Klasse A2/MS (62005252), VdS zugelassener universal Wärmemelder UTD 523 Klasse B (20202149), VdS zugelassener universal Wärmemelder UTD 523 Klasse B/MS (62005253), VdS zugelassener lichtoptischer Rauchmelder MSD 523 (20202139), VdS zugelassener lichtoptischer Rauchmelder MSD 523/MS (62005300), Meldersockel USB 501-6 (20202135), Ballwurfschutz BWS-9 für automatische Melder (20202214), UP-Einbauset Kompaktzentrale 4A/2A (13362501405), Service Port USB Konfigurationskabel inkl. Software (3000100) ,

note for installation

Das Zusatzmodul RWA-Bedienstelle TRZ/RBH Basic ist nicht nachrüstbar.

Zur Unterputzmontage wird ein UP-Rahmen benötigt (bitte separat bestellen)



note

The Service Port Software is required for extended configuration possibilities.
Please order separately.
 

Go back